VRV Water-to-air heat pump

36 Makeup water (Used to fill the tank as well) Makeup water (Used to fill the tank as well) Expansion tank Temperature indicating controller Temperature indicating controller Temperature indicating controller * In order to use brine for the freezing protection, install the heat exchanger to break off the line concerned. * In order to provide two or more hydrothermal systems (e.g. mainly heating for the north side system and mainly cooling on the south side), integrate the multiple systems into a single system, thus allowing for the heat recovery even between the water vs. water systems. * It is recommended to provide a port used for the cleaning of horizontal drain pipes. *For RWEY models, provide interlock with the flow switch. (Through the pump operation signal, an operative flow switch is recommended.) * Use a hermestic cooling tower in terms of water quality control * On each floor, If multiple units are installed or the units are installed far away from each other, use horizontal reverse return piping or a constant flow control valve to prevent air drift. To BS unit To BS unit To BS unit To BS unit Cooling (mainly for cooling) Heating (mainly for cooling) Open/Closed of valve In-between seasons (cooling/heating combination) Operation mode T1 set value T2 set value T3 set value 15°C 33°C, 31°C 25°C 20°C 33°C, 31°C 40°C Pump Temperature controller Three-way valve (mixed type) Y strainer Flexible joint Pressure gauge Thermometer Flow switch Cooling tower (32°C/37°C) Typical Installation with heat recovery from multiple systems through water circuit