08_ECPEN25-500_Ventilation

588 With our wide capacity range and different control options, a variety of layout possibilities to match your application: J Pair layout: one or more outdoor units combined with 1 air handling unit J Multi layout: one outdoor unit combined with multiple air handling units J Mix layout: one outdoor unit combined with an air handling unit AND indoor units Multi layout One VRV heat pump connected to several AHUs J with Z, Z’ control and field supplied controls on AHU side. J not allowed for VRV H/R J no interlaced coil possible Pair layout One ERA or VRV heat pump (system) connected to one AHU through one refrigerant circuit J with W, X, Y, Z, Z’ control J not allowed for VRV H/R Several ERA or VRV heat pumps connected to the interlaced coil of one AHU through several refrigerant circuits J with W, X, Y control J not allowed for VRV H/R and VRV-i One VRV heat pump (system) connected to the interlaced coil of one AHU through several refrigerant circuits J with W, X, Y control J not allowed for VRV H/R and VRV-i Refrigerant piping F1-F2 P1-P2 Mix layout VRV indoor units and AHU(s) mixed in the same VRV heat pump or heat recovery system J with Z, Z’ control and field supplied controls on AHU side J no interlaced coil possible J hydrobox not possible Air Handling Unit kits Layout possibilities