201 1D128513 Detailed technical drawings RZAG-NV1/NY1 RZA-D Multiple rows of units ( ) HB HU b (mm) ≥1000 ≥100 ≥3000 ≥1500 b ≥100(1) HB HU ≥100(1) ≥100(1) ≥100(1) ≥100(1) ≥100(1) HB≤½HU b≥250 ½HU<HB≤HU b≥300 HB>HU (1) For better serviceability, use a distance ≥250 mm Stacked units (max. 2 levels) ( ) A1 A2 ≥500 ≥1000 A2 ≥500 ≥300 ≥100(1) ≥100(1) B1 A2 B2 ≥100 ≥300 B2 ≥100 ≥1000 B2 ≥100(1) ≥100(1) A1 A2 ≥500 ≥1000 A2 ≥500 ≥300 ≥100(1) ≥100(1) B1 A2 B2 ≥100 ≥300 B2 ≥100 ≥1000 B2 ≥100(1) ≥100(1) A1 A2 ≥500 ≥1000 A2 ≥500 ≥300 ≥100(1) ≥100(1) B1 A2 B2 ≥100 ≥300 B2 ≥100 ≥1000 B2 ≥100(1) ≥100(1) A1 A2 ≥500 ≥1000 A2 ≥500 ≥300 ≥100(1) ≥100(1) B1 A2 B2 ≥100 ≥300 B2 ≥100 ≥1000 B2 ≥100(1) ≥100(1) (1) For better serviceability, use a distance ≥250 mm A1=>A2 (A1) If there is danger of drainage dripping and freezing between the upper and lower units… (A2) Then install a roof between the upper and lower units. Install the upper unit high enough above the lower unit to prevent ice buildup at the upper unit’s bottom plate. B1=>B2 (B1) If there is no danger of drainage dripping and freezing between the upper and lower units… (B2) Then it is not required to install a roof, but seal the gap between the upper and lower units to prevent discharged air from flowing back to the suction side through the bottom of the unit. Click here to view all RZAG-NV1 technical drawings on my.daikin.eu Click here to view all RZAG-NY1 technical drawings on my.daikin.eu